Designed for single immersion tanks, the ICP40 features an integrated continuous-duty pump and adaptive fan control in a compact 140 × 70 × 40 cm enclosure. It delivers over 40 kW of heat transfer capacity at 35°C ambient (up to 50 kW at 25°C). The dual 500 mm fan module adjusts automatically to cooling demand, minimizing noise and energy use. Standard operation is 60–62 dB, with optional high-performance low-noise fans rated at 50–55 dB. Power consumption ranges from 400 W on average to 600 W at peak load.

Application
Single Immersion Mining Enclosure (8xS19 | 12 x M30/M50 Whatsminer)
Cooling capacity
(Ambient temp=35°C)
40 kW
Cooling capacity
(Ambient temp=25°C)
45kW
Dimensions
1400(W) x 460(D) x 715(H) mm
Fans
2 x 500 mm
Noise level [dB(A)]
58-62 dB(A)
Max power consumption
1.5 kW
Power Standard
230-240V/1Ph/50/60 Hz
Fittings
1" / DN25
Fluid temperature In / Out
60 / 40 °C
Transport weight
80 kg | 176 lb
Nominal volume flow
1.7 mᶾ/hf
Pressure drop
0.34 bar

This deployment showcases the DCX ICP40 Dry Cooler operating in a hybrid configuration for both heat rejection and heat reuse. The cooler is connected to a single immersion enclosure via insulated piping, forming a closed-loop circuit with an integrated pump that circulates the heated dielectric fluid.
What distinguishes this installation is its smart heat recovery strategy: instead of rejecting all thermal energy to the ambient air, part of the heat is repurposed to warm a swimming pool. In moderate climates or seasonal applications, this approach not only cools the hardware efficiently but also reduces operating costs by making productive use of the waste heat.

Would you like to order a specific product, or maybe you have an entire project at hand? In order to provide you with the best experience possible, we kindly ask you to include the following infromation in your message: