Dual loop, condensation safe hydro cooling
OVERVIEW
DCX offers a full range of cost-effective but enterprise class Coolant Distribution Units (CDUs) for hydro miners and direct liquid cooling system which support advanced and power hungry hydro miner models. We propose multiple CDU systems designed to fulfil specific requirements from small scale to large liquid cooling operations, including the in-rack CDU 1 & 2 models, as well as CDU 3, 6, 9, and 12 with a rated capacity from 300kW to 1200kW per single CDU system. These CDU’s are designed for high-powered miners or mining servers and offer advanced features such as variable-speed pumps, full condensation control, cooling loop separation, redundant components, adaptive operation, energy efficient cooling & intelligent controls with full remote control of the system.
DCX CDU’s, are a standalone, rack based Coolant Distribution Units (CDU), a key component in direct chip cooling (DLC) or hydro cooling systems. Those CDU’s with a rated cooling capacity from 300 to 1200 kW offer adaptive and efficient cooling of hydro miners with full condensation control. The CDU’s are designed to regulate the flow and temperature of coolant and ensure that each component in the cooling loop receives an adequate supply of flow to maintain the desired operating temperature. It is also responsible for monitoring the temperature of the coolant and adjusting the flow rate as necessary to maintain the temperature below the dew point protecting the precious electronics from condensation. DCX CDU’s provides effective separation of the facility circuit and secondary circuit which allows controlled fluid quality and ensures that the cooling fluid in a data centre environment can be kept to a minimum volume, is closely controlled for flow, pressure & temperature and can be accurately maintained for fluid quality.
Some of the key features of a DCX CDU’s include:
- High flow rate: designed to deliver a high flow rate of coolant to ensure that each component in the cooling loop receives an adequate supply of coolant.
- Full remote monitoring: contains temperature, flow and operation sensors that monitor the temperature of the coolant and adjust the flow rate as necessary to maintain a consistent temperature.
- Redundancy: designed with redundant pumps and other components to ensure that the cooling system remains operational in the event of a failure.
- Energy efficiency: CDU’s are designed to be energy-efficient, with features such as variable speed pumps and advanced control systems that help to minimize energy consumption.
Overall, our Coolant Distribution Units play a critical role in the operation of direct liquid cooling systems and hydro systems in data centres, helping to maintain the desired operating temperature and ensure the reliability and efficiency of the cooling system.
FEATURES
-
Enterprise class system & controls with full redundancy
-
Complete loop separation and condensation control
-
From 300kw to 1.2MW per single CDU
-
From 6 to 28 server racks per single CDU
CDU 3 – Liquid to Liquid Cooling Distribution Unit
DCX offers a full range of cost-effective but enterprise class Coolant Distribution Units (CDUs) for hydro miners and direct liquid cooling systems, including the in-rack CDU 1 & 2 models, as well as CDU 3, 6, 9, and 12 with a rated capacity from 300kW to 1200kW per single CDU system. These CDUs are designed for high-powered miners or mining servers and offer advanced features such as variable-speed pumps, full condensation control, cooling loop separation, redundant components, adaptive operation, energy efficient cooling & intelligent controls with full remote control of the system.
DCX CDU 3, a standalone, rack based Coolant Distribution Unit (CDU), is a key component in direct chip cooling (DLC) or hydro cooling systems. This CDU unit with a rated cooling capacity of 300kW offers adaptive and efficient cooling of hydro miners with full condensation control. The CDU is designed to regulate the flow and temperature of coolant and ensure that each component in the cooling loop receives an adequate supply of flow to maintain the desired operating temperature. It is also responsible for monitoring the temperature of the coolant and adjusting the flow rate as necessary to maintain the temperature below the dew point protecting the precious electronics from condensation. DCX CDU 3 provides effective separation of the facility circuit and secondary circuit which allows controlled fluid quality and ensures that the cooling fluid in a data centre environment can be kept to a minimum volume, is closely controlled for flow, pressure & temperature and can be accurately maintained for fluid quality.
Dual pump highly redundant design. It can be maintained without shutting down when the pump/power fails or the filter is clogged. The system has a comprehensive real-time monitoring function of operating parameters. The communication interface of upper computer adopts 2 redundant RS485 & 2 redundant RJ45, and the default communication protocol Modbus RTU & Modbus TCP/IP. Also it can be customized and modified according to the customer requirements.
General Spec
1 | 2 |
---|---|
Cooling Capacity | >300kW@AT=15℃ |
Primary Coolant | ASHRAE W4 (45℃) facility liquid |
AC Power | 3P AC380V±10% 50/60Hz |
Power Consumption | 4kW |
Dimension | 600*1200*2035 (W*D*H) |
Transport / wqwWet Weight | 450/560 kg |
Technical Specification
Rated cooling capacity (kW) | 300 | ||||||
Operation condition description | Working condition 1 | Working condition 2 | |||||
Primary side | Secondary side | Primary side | Secondary side | ||||
Coolant | DI-water | DI-water | PG-25 | PG-25 | |||
Flow (m3/h) | 18.9 | 18.9 | 18.9 | 18.9 | |||
Output rated dP (bar) | / | ≥7.2/0.5 | / | ≥7.2/0.5 | |||
Rated inlet temperature (°C) | 36 | 58.7 | 35 | 59.9 | |||
Rated outlet temperature (°C ) | 49.7 | 45 | 49.9 | 49.9 | |||
Cooling capacity margin | 23% | 19% | |||||
Height (mm) | Width (mm) | Depth (mm) | 2280 | 900 | 1300 | ||||||
Transport weight (kg / lbs) | 970 / 2138 | 1065 / 2348 | |||||
Operation weight (kg / lbs) | 1180/ 2601 | 1370 / 3020 | |||||
Max. power (kW) | 4 kW | ||||||
T-V coefficient (C*L) | 3.2×104 | ||||||
Power specifications | 3P AC380V 50/60Hz | ||||||
Working environment T&H | 0~50°/ RH5~85% | ||||||
Noise Level | 65dB(A) |
FEATURES
-
Enterprise class system & controls with full redundancy
-
Complete loop separation and condensation control
-
From 300kw to 1.2MW per single CDU
-
From 6 to 28 server racks per single CDU
CDU 6 – Liquid to Liquid Cooling Distribution Unit
DCX offers a full range of cost-effective but enterprise class Coolant Distribution Units (CDUs) for hydro miners and direct liquid cooling systems, including the in-rack CDU 1 & 2 models, as well as CDU 3, 6, 9, and 12 with a rated capacity from 300kW to 1200kW per single CDU system. These CDUs are designed for high-powered miners or mining servers and offer advanced features such as variable-speed pumps, full condensation control, cooling loop separation, redundant components, adaptive operation, energy efficient cooling & intelligent controls with full remote control of the system.
DCX CDU 6, a standalone, rack based Coolant Distribution Unit (CDU), is a key component in direct chip cooling (DLC) or hydro cooling systems. This CDU unit with a rated cooling capacity of 600kW offers adaptive and efficient cooling of hydro miners with full condensation control. The CDU is designed to regulate the flow and temperature of coolant and ensure that each component in the cooling loop receives an adequate supply of flow to maintain the desired operating temperature. It is also responsible for monitoring the temperature of the coolant and adjusting the flow rate as necessary to maintain the temperature below the dew point protecting the precious electronics from condensation. DCX CDU 6 provides effective separation of the facility circuit and secondary circuit which allows controlled fluid quality and ensures that the cooling fluid in a data centre environment can be kept to a minimum volume, is closely controlled for flow, pressure & temperature and can be accurately maintained for fluid quality.
Dual pump highly redundant design. It can be maintained without shutting down when the pump/power fails or the filter is clogged. The system has a comprehensive real-time monitoring function of operating parameters. The communication interface of upper computer adopts 2 redundant RS485 & 2 redundant RJ45, and the default communication protocol Modbus RTU & Modbus TCP/IP. Also it can be customized and modified according to the customer requirements.
General Spec
1 | 2 |
---|---|
Cooling Capacity | 600kW@AT=15℃ |
Primary Coolant | ASHRAE W4 (45℃) facility liquid |
AC Power | 3P AC380V±10% 50/60Hz |
Power Consumption | 7-11kW |
Dimension | 900*1300*2280 (W*D*H) |
Transport / wqwWet Weight | 1180/1370 kg |
Technical Specification
Rated cooling capacity (kW) | IB600****AT10 | ||||||
---|---|---|---|---|---|---|---|
Product Model | IB600****AT10 | IB600****AT10 | |||||
Operation condition | Primary side | Secondary side | Primary side | Secondary side | |||
Coolant | Facility-water | DI-water | Facility-water | DI-water | |||
Flow (m3/h) | 35 | 35 | 35 | 35 | |||
Output rated dP (bar) | / | ≥2.8 | / | ≥3.2 | |||
Rated inlet temperature (°C) | 35 | 65 | 35 | 52.7 | |||
Rated outlet temperature (°C ) | 50 | 45 | 49.6 | 38 | |||
Cooling capacity margin | 20% | -1.5% | |||||
Height (mm) | Width (mm) | Depth (mm) | 2280 | 900 | 1300 | ||||||
Transport weight (kg / lbs) | 970 / 2138 | 1065 / 2348 | |||||
Operation weight (kg / lbs) | 1180/ 2601 | 1370 / 3020 | |||||
Max. power (kW) | 7 (Pump3004) / 11 (Pump4604) | ||||||
T-V coefficient (C*L) | 4.8×104 | ||||||
Power specifications | 3P AC380V 50/60Hz | ||||||
Working environment T&H | 0~50°/ RH5~85% | ||||||
Noise Level | 65dB(A) |
FEATURES
-
Enterprise class system & controls with full redundancy
-
Complete loop separation and condensation control
-
From 300kw to 1.2MW per single CDU
-
From 6 to 28 server racks per single CDU
CDU 9 – Liquid to Liquid Cooling Distribution Unit
DCX offers a full range of cost-effective but enterprise class Coolant Distribution Units (CDUs) for hydro miners and direct liquid cooling systems, including the in-rack CDU 1 & 2 models, as well as CDU 3, 6, 9, and 12 with a rated capacity from 300kW to 1200kW per single CDU system. These CDUs are designed for high-powered miners or mining servers and offer advanced features such as variable-speed pumps, full condensation control, cooling loop separation, redundant components, adaptive operation, energy efficient cooling & intelligent controls with full remote control of the system.
DCX CDU 9, a standalone, rack based Coolant Distribution Unit (CDU), is a key component in direct chip cooling (DLC) or hydro cooling systems. This CDU unit with a rated cooling capacity of 900kW offers adaptive and efficient cooling of hydro miners with full condensation control. The CDU is designed to regulate the flow and temperature of coolant and ensure that each component in the cooling loop receives an adequate supply of flow to maintain the desired operating temperature. It is also responsible for monitoring the temperature of the coolant and adjusting the flow rate as necessary to maintain the temperature below the dew point protecting the precious electronics from condensation. DCX CDU 9 provides effective separation of the facility circuit and secondary circuit which allows controlled fluid quality and ensures that the cooling fluid in a data centre environment can be kept to a minimum volume, is closely controlled for flow, pressure & temperature and can be accurately maintained for fluid quality.
Dual pump highly redundant design. It can be maintained without shutting down when the pump/power fails or the filter is clogged. The system has a comprehensive real-time monitoring function of operating parameters. The communication interface of upper computer adopts 2 redundant RS485 & 2 redundant RJ45, and the default communication protocol Modbus RTU & Modbus TCP/IP. Also it can be customized and modified according to the customer requirements.
General Spec
1 | 2 |
---|---|
Cooling Capacity | 900kW@AT=15℃ |
Primary Coolant | ASHRAE W4 (45℃) facility liquid |
AC Power | 3P AC380V±10% 50/60Hz |
Power Consumption | 11kW |
Dimension | 9500*1500*2213 (W*D*H) |
Transport / wqwWet Weight | 1390/1610 kg |
Technical Specification
Rated cooling capacity (kW) | IB600****AT10 | ||||||
---|---|---|---|---|---|---|---|
Rated cooling capacity (kW) | 900 | ||||||
Product Model | IB900****AT10 | IB900****AT03 | |||||
Operation condition | Primary side | Secondary side | Primary side | Secondary side | |||
Coolant | Facility-water | DI-water | Facility-water | DI-water | |||
Flow (m3/h) | 52 | 52 | 52 | 52 | |||
Output rated dP (bar) | / | ≥2.8 | / | ≥3.2 | |||
Rated inlet temperature (°C) | 35 | 63.1 | 35 | 52.8 | |||
Rated outlet temperature (°C ) | 53 | 45 | 49.8 | 38 | |||
Cooling capacity margin | 20% | -1.5% | |||||
Height (mm) | Width (mm) | Depth (mm) | 2035 | 600 | 1200 | ||||||
Transport weight (kg / lbs) | 1090 / 2403 | 1223 / 2696 | |||||
Operation weight (kg / lbs) | 1390 / 3064 | 1610 / 3549 | |||||
Max. power (kW) | 11 | ||||||
T-V coefficient (C*L) | 4.8×104 | ||||||
Power specifications | 3P AC380V 50/60Hz | ||||||
Working environment T&H | 0~50°/ RH5~85% | ||||||
Noise Level | 65dB(A) |
FEATURES
-
Enterprise class system & controls with full redundancy
-
Complete loop separation and condensation control
-
From 300kw to 1.2MW per single CDU
-
From 6 to 28 server racks per single CDU
CDU 12 – Liquid to Liquid Cooling Distribution Unit
DCX offers a full range of cost-effective but enterprise class Coolant Distribution Units (CDUs) for hydro miners and direct liquid cooling systems, including the in-rack CDU 1 & 2 models, as well as CDU 3, 6, 9, and 12 with a rated capacity from 300kW to 1200kW per single CDU system. These CDUs are designed for high-powered miners or mining servers and offer advanced features such as variable-speed pumps, full condensation control, cooling loop separation, redundant components, adaptive operation, energy efficient cooling & intelligent controls with full remote control of the system.
DCX CDU 12, a standalone, rack based Coolant Distribution Unit (CDU), is a key component in direct chip cooling (DLC) or hydro cooling systems. This CDU unit with a rated cooling capacity of 1200kW offers adaptive and efficient cooling of hydro miners with full condensation control. The CDU is designed to regulate the flow and temperature of coolant and ensure that each component in the cooling loop receives an adequate supply of flow to maintain the desired operating temperature. It is also responsible for monitoring the temperature of the coolant and adjusting the flow rate as necessary to maintain the temperature below the dew point protecting the precious electronics from condensation. DCX CDU 12 provides effective separation of the facility circuit and secondary circuit which allows controlled fluid quality and ensures that the cooling fluid in a data centre environment can be kept to a minimum volume, is closely controlled for flow, pressure & temperature and can be accurately maintained for fluid quality.
Dual pump highly redundant design. It can be maintained without shutting down when the pump/power fails or the filter is clogged. The system has a comprehensive real-time monitoring function of operating parameters. The communication interface of upper computer adopts 2 redundant RS485 & 2 redundant RJ45, and the default communication protocol Modbus RTU & Modbus TCP/IP. Also it can be customized and modified according to the customer requirements.
General Spec
1 | 2 |
---|---|
Cooling Capacity | >1200kW@AT=15℃ |
Primary Coolant | ASHRAE W4 (45℃) facility liquid |
AC Power | 3P AC380V±10% 50/60Hz |
Power Consumption | 13kW |
Dimension | 950*1500*2265 (W*D*H) |
Transport / wqwWet Weight | 1600/1850 kg |
Technical Specification
Rated cooling capacity (kW) | IB600****AT10 | ||||||
---|---|---|---|---|---|---|---|
Rated cooling capacity (kW) | 1200 | ||||||
Product Model | IB1200****AT10 | IB1200****AT03 | |||||
Operation condition | Primary side | Secondary side | Primary side | Secondary side | |||
Coolant | Facility-water | DI-water | Facility-water | DI-water | |||
Flow (m3/h) | 73 | 73 | 73 | 73 | |||
Output rated dP (bar) | / | ≥2.0 | / | ≥2.0 | |||
Rated inlet temperature (°C) | 35 | 59.3 | 35 | 52.8 | |||
Rated outlet temperature (°C ) | 53 | 45 | 49.8 | 38 | |||
Cooling capacity margin | 28% | 4% | |||||
Height (mm) | Width (mm) | Depth (mm) | 2265 | 950 | 1500 | ||||||
Transport weight (kg / lbs) | 1600 / 3527.4 | 1745 / 3847 | |||||
Operation weight (kg / lbs) | 1850 / 4078.6 | 2019 / 4451 | |||||
Max. power (kW) | 13 | ||||||
T-V coefficient (C*L) | 6.4×104 | ||||||
Power specifications | 3P AC380V 50/60Hz | ||||||
Working environment T&H | 0~50°/ RH5~85% | ||||||
Noise Level | 65dB(A) |
FEATURES
-
Enterprise class system & controls with full redundancy
-
Complete loop separation and condensation control
-
From 300kw to 1.2MW per single CDU
-
From 6 to 28 server racks per single CDU
OVERVIEW
DCX offers a full range of cost-effective but enterprise class Coolant Distribution Units (CDUs) for hydro miners and direct liquid cooling system which support advanced and power hungry hydro miner models. We propose multiple CDU systems designed to fulfil specific requirements from small scale to large liquid cooling operations, including the in-rack CDU 1 & 2 models, as well as CDU 3, 6, 9, and 12 with a rated capacity from 300kW to 1200kW per single CDU system. These CDU’s are designed for high-powered miners or mining servers and offer advanced features such as variable-speed pumps, full condensation control, cooling loop separation, redundant components, adaptive operation, energy efficient cooling & intelligent controls with full remote control of the system.
DCX CDU’s, are a standalone, rack based Coolant Distribution Units (CDU), a key component in direct chip cooling (DLC) or hydro cooling systems. Those CDU’s with a rated cooling capacity from 300 to 1200 kW offer adaptive and efficient cooling of hydro miners with full condensation control. The CDU’s are designed to regulate the flow and temperature of coolant and ensure that each component in the cooling loop receives an adequate supply of flow to maintain the desired operating temperature. It is also responsible for monitoring the temperature of the coolant and adjusting the flow rate as necessary to maintain the temperature below the dew point protecting the precious electronics from condensation. DCX CDU’s provides effective separation of the facility circuit and secondary circuit which allows controlled fluid quality and ensures that the cooling fluid in a data centre environment can be kept to a minimum volume, is closely controlled for flow, pressure & temperature and can be accurately maintained for fluid quality.
Some of the key features of a DCX CDU’s include:
- High flow rate: designed to deliver a high flow rate of coolant to ensure that each component in the cooling loop receives an adequate supply of coolant.
- Full remote monitoring: contains temperature, flow and operation sensors that monitor the temperature of the coolant and adjust the flow rate as necessary to maintain a consistent temperature.
- Redundancy: designed with redundant pumps and other components to ensure that the cooling system remains operational in the event of a failure.
- Energy efficiency: CDU’s are designed to be energy-efficient, with features such as variable speed pumps and advanced control systems that help to minimize energy consumption.
Overall, our Coolant Distribution Units play a critical role in the operation of direct liquid cooling systems and hydro systems in data centres, helping to maintain the desired operating temperature and ensure the reliability and efficiency of the cooling system.
FEATURES
-
Enterprise class system & controls with full redundancy
-
Complete loop separation and condensation control
-
From 300kw to 1.2MW per single CDU
-
From 6 to 28 server racks per single CDU
Get in Touch & Get the Quote
We’d love to help you in your project with our liquid cooling systems.
We need more info:
We need basic information required to size the DCX Immersion Mining system correctly:
- type and number of ASIC miners or GPUs
- expected miners power
- your plan for heat rejection – we can deliver immersion optimized
- dry cooler or connection to local water loop
- city / country of your operation – to make sure w will deliver
- expected performance in your maximum ambient temperature and to quote shipping cost.